Indoor Environmental Quality Guidelines

« Previous Guideline | Next Guideline »

I.4 Ventilation Design

Intent
Promote good indoor air quality by requiring a ventilation baseline based on the general procedures and information contained in the latest approved version of ASHRAE Standard 62.1. Encourage better indoor air quality by recommending that, in addition, ventilation design intent be demonstrated on a regular basis to building owners and operators. Encourage best indoor air quality by further recommending adjusting ventilation requirements upward from the baseline based on setting target CO2 concentration maxima.

Required Performance Criteria

  1. Radon is best controlled using source prevention techniques rather than ventilation. For New Buildings Path, if construction is to occur in one of the 68 Minnesota counties considered "Zone 1" by the US EPA, guidance contained in the EPA document, "Radon Prevention in the Design and Construction of Schools and other Large Buildings", must be followed. Major Renovations located in these 68 counties whose exterior envelopes have more than 40% of their surface areas in contact with the ground must follow the same EPA guidance.
  2. Ventilation Baseline: meet current ASHRAE ventilation standard 62.1 for commercial and institutional buildings (as of the writing of this guideline ASHRAE 62.1-2010 Updates are scheduled to be issued every three years thereafter.)

Recommended Performance Criteria

  1. Ventilation Performance Validation: in addition to required ventilation baseline criteria above, design the ventilation system so that CO2 concentrations can be monitored continuously in all continuously occupied spaces. Continuously occupied spaces are those intended for human occupancy excluding spaces intended for other purposes such as storage rooms or equipment rooms. Compare the expected values of CO2 concentrations found in high-occupancy spaces* in the building with those expected from the building design using ASHRAE 62.1. This should be done at three-month intervals during the initial year of occupancy and annually thereafter.
  2. Carbon Dioxide Limits on Ventilation: in addition to required and recommended criteria within this guideline above design the ventilation system so that they CO2 concentration in continuously occupied breathing zones (defined as the volume between 3 and 72 inches above the floor and 2 feet or greater distance from walls) shall not exceed 450 ppm above outdoor concentrations. Compare the expected values of CO2 concentrations found in high-occupancy spaces* in the building with those expected from the building design using ASHRAE 62.1 supplemented by the more rigorous CO2 concentration limit of this guideline (I.4D). Do this at three-month intervals during the initial year of occupancy and annually thereafter.

* Note: For this guideline, “high-occupancy spaces” are defined as spaces in the building with normal occupancy densities higher than the average density for the entire building.

Compliance Tools and Resources

  • For Item A: US EPA, Radon zone map: www.epa.gov/iaq/radon/zonemap.html
  • For Item A: US EPA, "Radon Prevention in the Design and Construction of Schools and other Large Buildings", EPA document 625-R-92-016, June 1994. www.epa.gov/iaq/radon.pubs/index.html
  • For Items B, C, D: Reference Standard: ASHRAE (2007). ANSI/ASHRAE Standard 62.1-2007: Ventilation for acceptable indoor air quality. Atlanta, GA, USA, American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc.
  • For Items B, C, D: ASHRAE (2005). 62.1 User's Manual, ANSI/ASHRAE Standard 62.1-2007, Ventilation for Acceptable Indoor Air Quality. Atlanta, GA, ASHRAE.
  • For Item D: B3 Guidelines Appendix I-4 Calculating CO2 Concentrations in a Zone

Related B3 Guidelines Documents

Supplemental Resources
For I.4C and D:
There is a robust literature examining the technique of monitoring CO2 concentrations in a space and using that information to extract information about the ventilation delivered to the space. The literature comparing design and performance of ventilation systems in commercial buildings, on the other hand, is modest. Readers should consult the 2006 paper by Persily for further perspectives. This paper is based on an invited plenary presentation he made at the Indoor Air 05 conference in Beijing, China in Sept 2005.

  • Persily, A. (1997.) "Evaluating building IAQ and ventilation with indoor carbon dioxide." ASHRAE Transactions 103(2.)
  • Schell, M. B., S. C. Turner, et al. (1998.) "Application of CO2-based demand-controlled ventilation using ASHRAE Standard 62: Optimizing energy use and ventilation." ASHRAE Transactions 104(2): Paper TO-98-21-1.
  • Persily, A. (2006). "What we think we know about ventilation." Ventilation: submitted for publication.

For I.4D:
The choices about CO2 concentrations come from many sources. Primary are the studies that relate CO2 concentrations to ventilation rates and to occupant complaints. A representative collection of references are:

  • Apte, M. G., W. Fisk, et al. (2000.) "Associations between indoor CO2 concentrations and sick building syndrome symptoms in US office buildings: An analysis of the 1994-96 BASE study." Indoor Air 10: 246-257.
  • Engvall, K., P. Wickman, et al. (2005). "Sick building syndrome and perceived indoor environment in relation to energy saving by reduced ventilation flow during heating season: 1 year intervention study in dwellings." Indoor Air 15(2): 120-126.
  • Mumma, S (2004.) Transient occupancy ventilation by monitoring CO2, IAQ Applications, 5(1): pgs. 21-23.
  • Persily, A. (1997.) "Evaluating building IAQ and ventilation with indoor carbon dioxide." ASHRAE Transactions 103(2.)
  • Schell, M. B., S. C. Turner, et al. (1998.) "Application of CO2-based demand-controlled ventilation using ASHRAE Standard 62: Optimizing energy use and ventilation." ASHRAE Transactions 104(2): Paper TO-98-21-1.
  • Seppänen, O. A., W. J. Fisk, et al. (1999.) "Association of ventilation rates and CO2 concentrations with health and other responses in commercial and institutional buildings." Indoor Air-International Journal of Indoor Air Quality and Climate 9(4): 226-52.
  • Sundell, J., T. Lindvall, et al. (1994.) "Associations between type of ventilation and airflow rates in office buildings and the risk of SBS-symptoms among occupants." Environment International 20: 239-251.
  • Wargocki, P., D. P. Wyon, et al. (2000.) "The effects of outdoor air supply rate in an office on perceived air quality, sick building syndrome (SBS) symptoms and productivity." Indoor Air-International Journal of Indoor Air Quality and Climate 10(4): 222-36.
  • Wargocki, P., J. Sundell, et al. (2002.) "Ventilation and health in non-industrial indoor environments: Report from a European Multidisciplinary Scientific Consensus Meeting (EUROVEN.)" Indoor Air-International Journal of Indoor Air Quality and Climate 12(2): 113-28

« Previous Guideline | Next Guideline »