Guidelines Home | v3.2r02 | v3.1 | v3.0 | v2.2 | Training | Documents | Previous Versions
Guideline I.2: Moisture and Water Control
Intent
To ensure a moisture-safe building envelope.
Required Performance Criteria
Guidelines I.2A and I.2C are required for New Construction and Major Renovation projects with an exterior envelope included in the project scope. Guidelines I.2B is required for projects that include 20,000 gsf or more of conditioned space with an exterior envelope included in the project scope. Guideline I.2B is recommended for smaller projects, particularly those with high R-value enclosures.
- Bulk Water Management
Implement the following to ensure adequate control of bulk water on the site:- Site grading at building perimeter: Ensure 5% slope away from the building for a minimum of 10 ft. in unpaved and nonpedestrian areas.
- Use downspout leaders, trench drains, and/or other methods to direct runoff from the building away from the perimeter.
- Ensure irrigation systems do not spray on the building enclosure.
- Moisture-safe design:
Design the building envelope to manage moisture flow and maintain all layers of wall and roof assemblies at safe moisture levels by implementing items listed below.- For above-grade walls: Project teams must demonstrate safe moisture design by conducting a qualitative moisture analysis, and by conducting one of two quantitative moisture analysis options. Analysis must be performed for at least two wall assemblies or one wall assembly if it comprises 60% or more of the total wall area. Wall types following the principles of the “Perfect Wall” with all control layers (water, air, vapor, thermal) outboard of the sheathing (i.e. no cavity insulation) do not require the quantitative moisture analysis.
Qualitative moisture analysis:
This analysis shall be guided by the B3 Qualitative Moisture Analysis Worksheet for walls, discussing how the assembly manages liquid water, capillary drive, air leakage, and vapor diffusion, including location and type of each control layer: water, air, vapor, and thermal.
Quantitative moisture analysis:- Option 1: Static temperature and vapor pressure profile calculation (Glaser method):Project teams are encouraged to use the B3 Glaser Calculator Tool. Results must show each surface layer through the wall section remains below the saturation vapor pressure. Test conditions for this analysis must use the average exterior winter temperature and humidity (average of the coldest three months) at or near the project site. Different buildings and space types will have varying interior temperature and humidity levels. To create a safety margin, this analysis shall use challenging conditions; the highest interior temperature and humidity the exterior wall is likely to experience on a regular basis.
- Option 2: Dynamic moisture simulation (i.e., WUFI software): An analysis following American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) 160 must show the wall’s total moisture content achieves a declining or stable moisture content pattern over three years while the sheathing meets the mold growth criterion of ASHRAE 160-2009. This criterion verifies that the highest 30-day running average surface relative humidity in the sheathing is below 80% when surface temperatures are between 41°F and 104°F.
- For above-grade walls: Project teams must demonstrate safe moisture design by conducting a qualitative moisture analysis, and by conducting one of two quantitative moisture analysis options. Analysis must be performed for at least two wall assemblies or one wall assembly if it comprises 60% or more of the total wall area. Wall types following the principles of the “Perfect Wall” with all control layers (water, air, vapor, thermal) outboard of the sheathing (i.e. no cavity insulation) do not require the quantitative moisture analysis.
- Moisture-safe construction: Air leakage and resulting condensation is one of the primary causes of moisture damage in buildings. Construct the building to control air leakage. Compliance with this guideline can be achieved using one of the two following methods:
- Whole-building air tightness test: Test the building thermal envelope for air tightness using the Air Barrier Association of America (ABAA) Standard Method for Building Enclosure Airtightness Compliance Testing “operational enclosure test.” A pressurization test is not required, but may be performed in addition to the required depressurization test. The maximum air leakage rate allowed is 0.25 cubic feet per minute (cfm) per square foot enclosure area (6-sided) at 75 Pascal (Pa).[1] If the rate falls above this level, a diagnostic evaluation to find the primary sources of air leakage is required using smoke tracer or infrared imaging, followed by nondestructive remediation steps to reduce air leakage. A final air tightness test is required following remediation efforts. If the final leakage rate achieved is below 0.4 cfm per sq. ft. at 75 Pa, the building is considered compliant with this guideline.
- Third-party building enclosure consultant:The building enclosure must be designed and constructed with assistance from a third-party building enclosure consultant. This scope of work must include, but is not limited to:
- Regularly scheduled meetings and consultations with the design and construction team during each phase (Predesign through construction and project completion).
- Review of all technical plans, specifications, shop drawings, and material submittals relating to the building enclosure.
- Coordination, observation, and documentation of preconstruction training for enclosure contractors and construction managers, focused on proper installation methods for air and water barrier continuity. (The training may be conducted by a qualified third party such as a manufacturer/product representative.)
- Coordination, observation, and documentation of air and water leakage performance testing on window installation mockup and/or field installations. This performance testing may be conducted by a third-party testing agency.
- Field observation of critical enclosure details for quality assurance during construction.
If compliance is achieved through a third-party building enclosure consultant, whole-building airtightness testing is not required as part of the process, though smaller scale assembly or panel testing may be appropriate as determined by the building enclosure consultant. Note that the building enclosure consultant may also perform the work required under Section B, Moisture-Safe Design. Note that a certified building enclosure consultant is preferred, though not required.